Rating from 800VA to 5KVA, Otima provides server-grade full power protection from power failure, spikes and surge in small footprint with powerful output power factor 0.9. This series is perfect for networking, telecom, server and mission-critical applications.
Overview
Main Features
- Pure sine wave
- Output power factor 0.9
- Programmable power management outlets
- ECO (Efficiency Corrective Optimizer) operation for energy saving
- Very high efficiency in battery mode
- Boost and Buck AVR for voltage stabilization
- Multiple communications available
- 3-stage smart battery charging control
- Optional HID Power Device USB Port
Specifications
| MODEL | Otima II T 800 | Otima II T 1.1K | Otima II T 1.5K | Otima II T 2K | Otima II T 2.5K | Otima II T 3K | |
| CAPACITY | 800 VA / 720 W | 1100 VA / 990 W | 1500 VA / 1350 W | 2000 VA / 1800 W | 2500 VA / 2250 W | 3000 VA / 2700 W | |
| INPUT | |||||||
| Nominal Voltage | 110/115/120/127 VAC or 208/220/230/240 VAC | ||||||
| Acceptable Voltage Range | 81-152 VAC or 162-290 VAC | ||||||
| Frequency Range | 60/50 Hz (auto sensing) | ||||||
| OUTPUT | |||||||
| Output Voltage | 110/115/120/127 VAC or 208/220/230/240 VAC | ||||||
| Frequency Range (Batt. Mode) | 50 Hz or 60 Hz ± 1 Hz | ||||||
| Transfer Time | Typical 2-6 ms, 10ms max. | ||||||
| Waveform (Batt. Mode) | Pure Sine Wave | ||||||
| Voltage Regulation (Batt. Mode) | ± 1.5% (before battery alarm) | ||||||
| Current Crest Ratio | 3:1 | ||||||
| Harmonic Distortion | 2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm) | ||||||
| EFFICIENCY | |||||||
| Battery Mode | ≧ 88%, up to 90% @ nominal battery voltage | ≧89%, up to 91% @ nominal battery voltage for 110/115/120/127 VAC ≧91%, up to 92% @ nominal battery voltage for 208/220/230/240 VAC | |||||
| Buck & Boost Mode | 95% | ||||||
| ECO Mode | 97% | ||||||
| BATTERY | |||||||
| Charging Voltage | 27.4 VDC ± 1% | 54.8 VDC ± 1% | 82.1 VDC ± 1% | ||||
| Charging Current (max.) | 1.5 A | ||||||
| Typical Recharge Time | 4 hours recover to 90% capacity | ||||||
| Battery Type & Numbers | 12 V/7 Ah x 2 | 12 V/9 Ah x 2 | 12 V/7 Ah x 4 | 12 V/9 Ah x 4 | 12 V/7 Ah x 6 | 12 V/9 Ah x 6 | |
| PROTECTION | |||||||
| Full Protection | Overload, discharge, and overcharge protection | ||||||
| INDICATORS | |||||||
| LCD Display | AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault, and Low Battery | ||||||
| ALARM | |||||||
| Battery Mode | Sounding every 10 seconds | ||||||
| Low Battery | Sounding every 2 seconds | ||||||
| Overload | Sounding every second | ||||||
| Fault | Continuously sounding | ||||||
| ENVIRONMENT | |||||||
| Operating Humidity | 0~90% RH @ 0- 40°C (non-condensing) | ||||||
| Noise Level | Less than 45dB | ||||||
| PHYSICAL | |||||||
| Net Weight (kgs) | 11.7 | 12.1 | 17.2 | 19.7 | 26.6 | 29 | |
| Dimension, DXWXH (mm) | 397 x 145 x 220 | 455 x 145 x 220 | 421 x 190 x 318 | ||||
| MANAGEMENT | |||||||
| Optional SNMP | Power management from SNMP manager and web browser | ||||||
| Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC | ||||||
| Model | Otima II T 5K | |
| CAPACITY | 5000 VA / 4500 W | |
| INPUT | ||
| Nominal Voltage | 208/220/230/240 VAC | |
| Acceptable Voltage Range | 162-290 VAC | |
| Frequency Range | 60/50 Hz (auto sensing) | |
| OUTPUT | ||
| Output Voltage | 208/220/230/240 VAC | |
| Frequency Range (Batt. Mode) | 50 Hz or 60 Hz ± 1 Hz | |
| Transfer Time | Typical 2-6 ms, 10ms max. | |
| Waveform (Batt. Mode) | Pure Sine Wave | |
| Voltage Regulation (Batt. Mode) | ± 1.5% (before battery alarm) | |
| Current Crest Ratio | 3:1 | |
| Harmonic Distortion | 2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm) | |
| EFFICIENCY | ||
| Battery Mode | ≧91%, up to 92% @ nominal battery voltage | |
| Buck & Boost Mode | 95% | |
| ECO Mode | 97% | |
| BATTERY | ||
| Charging Voltage | 82.1 VDC ± 1% | |
| Charging Current (max.) | 1.5 A | |
| Typical Recharge Time | 4 hours recover to 90% capacity | |
| Battery Type & Numbers | 12 V/10 Ah x 6 | |
| PROTECTION | ||
| Full Protection | Overload, discharge, and overcharge protection | |
| INDICATORS | ||
| LCD Display | AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault, and Low Battery | |
| ALARM | ||
| Battery Mode | Sounding every 10 seconds | |
| Low Battery | Sounding every 2 seconds | |
| Overload | Sounding every second | |
| Fault | Continuously sounding | |
| ENVIRONMENT | ||
| Operating Humidity | 0~90% RH @ 0- 40°C (non-condensing) | |
| Noise Level | Less than 45dB | |
| PHYSICAL | ||
| Net Weight (kgs) | 34.5 | |
| Dimension, DXWXH (mm) | 421 x 190 x 318 | |
| MANAGEMENT | ||
| Optional SNMP | Power management from SNMP manager and web browser | |
| Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC | |
Downloads