Prime line interactive UPS built-in Boost AVR (Automatic Voltage Regulation) guarantees stable voltage, and its off-mode charging provides sufficient backup power for PCs, networking, monitors, POS and other sensitive electronic appliances.
Overview
Main Features
- 550VA/700VA/850VA/1000VA/1200VA/1350VA/1500VA simulated sine wave output
- Boost AVR for voltage stabilization
- Comprehensive LCD for real-time UPS status
- Provides battery backup and surge protected outputs
- Easy replacement battery compartment
- Optional hot-swappable battery design
- ENERGY STAR qualified for 120Vac models
- Built-in USB com. port and RJ-45 network protect
- Opional coax surge protection for TV antenna
- Optional 5V USB charger port for mobile devices
- Optional HID Power Device USB port
Specifications
MODEL | Prime 550 | Prime 700 | Prime 850 | Prime 1000 | Prime 1200 | Prime 1350 | |
CAPACITY | 550 VA / 330 W | 700 VA / 420 W | 850 VA / 510 W | 1000 VA / 600 W | 1200 VA / 720 W | 1350 VA / 810 W | |
INPUT | |||||||
Voltage | 110/120 VAC or 220/230/240 VAC | ||||||
Voltage Range | 81~132VAC / 86~142VAC or 162~270VAC / 170~270VAC / 176~270VAC | ||||||
Frequency Range | 50 Hz / 60 Hz ± 5 Hz (Auto Sensing) | ||||||
OUTPUT | |||||||
Voltage | 110/120 VAC or 220/230/240 VAC | ||||||
AC Voltage Regulation (Batt. Mode) | ± 5% | ||||||
Frequency Range (Batt. Mode) | 50 Hz or 60 Hz ± 1 Hz | ||||||
Transfer Time | 6ms typical, 10ms max | ||||||
Waveform (Batt. Mode) | Simulated Sine Wave | ||||||
BATTERY | |||||||
Battery Type & Number | 12 V/7 Ah x 1 | 12 V/9 Ah x 1 | 12 V/9 Ah x 2 | ||||
Typical Charging Time | 6-8 hours recover to 90% capacity | ||||||
PROTECTION | |||||||
Full Protection | Overload, discharge, output short circuit and overcharge protection | ||||||
INDICATORS | |||||||
LCD Display | Input/output voltage, Input/output frequency, Load level in VA, Load level in watts, Battery capacity and Estimated remaining runtime (Site wiring fault indicator only available for 110/120VAC) | ||||||
ALARM | |||||||
Battery Mode | Sounding every 10 seconds | ||||||
Low Battery | Sounding every second | ||||||
Overload | Sounding every 0.5 second | ||||||
Fault | Continuously sounding | ||||||
ENVIRONMENT | |||||||
Operating Humidity | 0~90% RH @ 0- 40°C (non-condensing) | ||||||
Noise Level | Less than 40dB | Less than 45dB | |||||
PHYSICAL | |||||||
Dimension, D X W X H (mm) | 288 x 99 x 280 | 410 x 99 x 280 | |||||
Net Weight (kgs) | 6.1 | 7.1 | 7.8 | 8.5 | 11.1 | 11.6 | |
MANAGEMENT | |||||||
Compliance & Standards | 110/120 VAC model: cTUVus (standard:UL 1778), FCC Part 15 Class B, ENERGY STAR (USA); 220/230/240VAC model: LVD: EN 62040-1, EMC: EN 62040-2 (Class B) | ||||||
Optional USB Port | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
Model | Prime 1500 | |
CAPACITY | 1500 VA / 900 W | |
INPUT | ||
Voltage | 110/120 VAC or 220/230/240 VAC | |
Voltage Range | 81~132VAC / 86~142VAC or 162~270VAC / 170~270VAC / 176~270VAC | |
Frequency Range | 50 Hz / 60 Hz ± 5 Hz (Auto Sensing) | |
OUTPUT | ||
Voltage | 110/120 VAC or 220/230/240 VAC | |
AC Voltage Regulation (Batt. Mode) | ± 5% | |
Frequency Range (Batt. Mode) | 50 Hz or 60 Hz ± 1 Hz | |
Transfer Time | 6ms typical, 10ms max | |
Waveform (Batt. Mode) | Simulated Sine Wave | |
BATTERY | ||
Battery Type & Number | 12 V/9 Ah x 2 | |
Typical Charging Time | 6-8 hours recover to 90% capacity | |
PROTECTION | ||
Full Protection | Overload, discharge, output short circuit and overcharge protection | |
INDICATORS | ||
LCD Display | Input/output voltage, Input/output frequency, Load level in VA, Load level in watts, Battery capacity and Estimated remaining runtime (Site wiring fault indicator only available for 110/120VAC) | |
ALARM | ||
Battery Mode | Sounding every 10 seconds | |
Low Battery | Sounding every second | |
Overload | Sounding every 0.5 second | |
Fault | Continuously sounding | |
ENVIRONMENT | ||
Operating Humidity | 0~90% RH @ 0- 40°C (non-condensing) | |
Noise Level | Less than 45dB | |
PHYSICAL | ||
Dimension, D X W X H (mm) | 410 x 99 x 280 | |
Net Weight (kgs) | 12 | |
MANAGEMENT | ||
Compliance & Standards | 110/120 VAC model: cTUVus (standard:UL 1778), FCC Part 15 Class B, ENERGY STAR (USA); 220/230/240VAC model: LVD: EN 62040-1, EMC: EN 62040-2 (Class B) | |
Optional USB Port | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
Downloads