APlus is the modular online UPS that provides high-efficiency value with a compact footprint and a flexible and scalable architecture, able to reach up to 600kW with only 10 modules. Hot-swappable modular design and built-in maintenance bypass switch enabling the system to be upgraded or repaired without powering down a mission-critical connected load.
Overview
Main Features
- 60KW single power module in 3U
- N+1 or N+X parallel redundancy for power guarantee
- Horizontal expansion by 1+1 cabinet parallel operation, up to 1.2MW
- Hot-swappable modular design decreases MTTR
- High scalability
- Built-in maintenance bypass switch for easy maintenance without interruptible
- High efficiency double conversion online UPS
- Flexible battery configuration and adjustable charging current
- High overload capability
- Power walk-in function
- Built-in dynamic password protection
- Built-in ultra communication slot
Specifications
MODEL | A+ 30U-120 | A+ 30U-180 | A+ 42U-300 | A+ 42U-420 | A+ 42U-480 | A+ 42U-600 | |
CABINET CAPACITY | 120KW | 180KW | 300KW | 420KW | 480KW | 600KW | |
PHASE | 3-phase in/3-phase out | ||||||
BATTERY TYPE | External Battery | ||||||
One Power Module Capacity | 60KVA/60KW | ||||||
Max. Power Module No. | 2 | 3 | 5 | 7 | 8 | 10 | |
INPUT | |||||||
Voltage Range | -30% ~ +20% | ||||||
Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | ||||||
Frequency Range | 40Hz ~70Hz | ||||||
Nominal Frequency | 50/60Hz (Auto sensing) | ||||||
Power Factor | > 0.99 at 100% load, >0.98 at 50% load | ||||||
Harmonic Distortion (THDi) | < 3% @ 100% load | ||||||
OUTPUT | |||||||
Nominal Frequency | 50/60Hz | ||||||
Overload Capability | 1 hour for ≦ 110%, 10 mins for 111% ~ 125%, 1 min for 126%~150% and 200ms for >150% | ||||||
Voltage Regulation (Steady state) | ≦± 1% Typical (balanced load) ; ≦± 2% Typical (unbalanced load) | ||||||
Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | ||||||
Efficiency | 0.96 | ||||||
Harmonic Distortion | ≦2% THD (Linear Load) ; ≦4% THD (Non-linear Load) | ||||||
Frequency Range (Synchronized range) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||||
ENVIRONMENT | |||||||
Altitude | <1000m for Nominal power | ||||||
IP Class | IP 20 | ||||||
Operation Temperature | 0 ~ 40℃ | ||||||
Relative Humidity | 0 ~ 95% non-condensing | ||||||
PHYSICAL | |||||||
Net Weight (kgs) | 308 | 352 | 516 | 654 | 932 | 1020 | |
Cabinet Dimension (D x W x H) mm |
1100 x 600 x 1475 | 1100 x 600 x 2010 | 1100 x 1200 x 2000 | ||||
MANAGEMENT | |||||||
Optional SNMP | Power management from SNMP manager and web browser | ||||||
Smart RS-232 / USB | Supports Windows® Family, Linux and MAC | ||||||
STANDARDS | |||||||
Safety | IEC/EN 62040-1 | ||||||
EMC | IEC/EN 62040-2 Category C3 | ||||||
BATTERY / CHARGER | |||||||
Nominal Voltage | +/- 192V ~ +/- 240V (Selectable) | ||||||
Maximum Voltage | +/- 240V (12V x 40 Pcs) | ||||||
Minimum Voltage | +/- 192V (12V x 32 Pcs) | ||||||
Floating Charge Voltage | 2.28V / Cell (2.25 ~2.33 Selectable) | ||||||
Boost Charging Voltage | 2.35V/Cell | ||||||
Temperature Compensation | Yes | ||||||
Maximum Charging Current (Per Power Module) | 18A (Adjustable) |