Outdoor UPS is designed for extreme demanding environments where clean backup power is needed. Built-in with AVR function, it helps to maintain normal operation without transferring to battery mode during voltage surge or sag. It also offers battery temperature sensor connector to monitor connected battery temperature anytime. Equipped with dry contacts, outdoor UPS is able to provide programmable signals for event alarms. It’s perfect to use in security, communication, traffic and many other critical industrial environments.
Overview
Main Features
- • Provide continuous power to critical loads during blackout in rugged environment
- • Wide operating temperature range from -40°C to 80°C suits for outdoor applications
- • Built-in boost and buck AVR to regulate input voltage
- • Selectable transfer time for normal or generator modes
- • Provide RS-232, USB and SNMP intelligent port
- • Circuit breaker protection on AC input, AC output and external battery input
- • User-adjustable charging current
- • Adjustable input threshold voltage
- • Provide programmable signals for dry contacts
- • Battery compensation optimizes battery lifecycle
Specifications
MODEL | Outdoor 2000A / UPS-2000A | Outdoor 2000E / UPS-2000E | |
Rated Power | 2000 VA / 1600 W | ||
INPUT | |||
Nominal Voltage | 120 VAC | 230/240 VAC | |
Acceptable Voltage Range | 88 ~152 VAC user programmable. Default: 100~130VAC | 176~300VAC user programmable. Default: 200~260VAC | |
Frequency Range | 60/50 Hz (Auto sensing) | ||
OUTPUT | |||
Transfer Time | Generator Mode (max.) | 25ms | |
Transfer Time | Normal Mode (max.) | 12ms | |
Waveform | Pure Sine Wave | ||
Nominal Voltage | 120 VAC | 230/240 VAC | |
Efficiency | AVR Mode | 90% | |
Efficiency | Battery Mode | 90% | |
Efficiency | Line Mode | 95% | |
Voltage Regulation (Batt. Mode) | 120 VAC ± 5% | 230/240 VAC ± 5% | |
Frequency | 50Hz/60Hz ± 0.1% | ||
THD (Batt. Mode) | <3% @ Full resistive load | ||
BATTERY | |||
Battery Type | AGM | ||
Charging Current | 2A/4A/6A/8A/10A (Adjustable) | ||
Low DC Warning Voltage | 46VDC ± 0.4VDC @ no load | ||
Nominal DC Voltage | 48 VDC | ||
INDICATORS | |||
Battery Mode | Green LED flashing | ||
Bypass Mode | Green LED on | ||
Fault without Output | Red LED on | ||
No Output | Green LED Off | ||
Warning with Output | Yellow LED on | ||
ENVIRONMENT | |||
Operating Temperature | -40°C to 80°C | -40°C to 70°C | |
Humidity | 5% to 95% Relative Humidity(Non-condensing) | ||
Noise Level | < 48dB | ||
PHYSICAL | |||
Dimension, D X W X H (mm) | 240 x400 x 133 | ||
Net Weight (kgs) | 13 | ||
Type of Mechanical Protection | IP 20 | ||
COMPLIANCE | |||
EMI Compliance | Class A FCC/CISPR [EN50091-2: 1995] | ||
Surge Protection | IEEE/ANSI C.62.41 & 2KV, L-N | ||
MANAGEMENT | |||
Communication | USB, RS-232 and optional SNMP | ||
Dry Contact Rating | 3A @ 125VAC | 3A @ 250VAC |