+Power E is a modular UPS system comprised of 1 to 3 modules of 30KW. This UPS is easily upgraded by users through adding plug-and-play 30KW power modules. Besides, this UPS system is stacked with battery pack as a tower for smaller footprint. It’s a perfect power solution for small-to-medium enterprise.
Overview
Main Features
- High efficiency online double conversion technology
- Output power factor 1
- Modular design lowers MTTR
- Adjustable battery numbers
- Adjustable charging current
- Built-in maintenance bypass switch for easy maintenance without interruption
- Graphic 5.7” LCD design for easy management
- Support 1+1 cabinets parallel
Specifications
MODEL | +Power E 15U-60 | +Power E 15U-90 | |
PHASE | 3-phase in/3-phase out | ||
Battery Type | External Battery | ||
Maximum CABINET CAPACITY | 60KW | 90KW | |
Maximum Power Module No. | 3 | ||
One Power Module Capacity | 20KVA/20KW | 30 KVA / 30 KW or 20 KVA / 20KW | |
INPUT | |||
Voltage Range | 305~478 VAC at 70%-100% load; 208~478 VAC for <70% load | ||
Nominal Voltage | 3 x 380VAC/400VAC/415VAC (3Ph+N) | ||
Frequency Range | 40Hz ~70Hz | ||
Nominal Frequency | 50/60 Hz (Auto sensing) | ||
Power Factor | > 0.99 at 100% load, >0.98 at 50% load | ||
Harmonic Distortion (THDi) | < 3% @ 100% load | ||
OUTPUT | |||
Nominal Frequency | 50/60Hz | ||
Overload Capability | 1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150% | ||
Voltage Regulation (Steady state) | ≦ ±1% Typical (balanced load); ≦ ±2% Typical (unbalanced load) | ||
Nominal Voltage | 3 x 380VAC/400VAC/415VAC (3Ph+N) | ||
Efficiency | Up to 94.5% | ||
Harmonic Distortion | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) | ||
Frequency Range (Synchronized range) | 46Hz~54Hz or 56Hz~64Hz | ||
BATTERY & CHARGER | |||
Floating Charge Voltage | 2.25V/Cell | ||
Boost Charging Voltage | 2.35V/Cell | ||
Maximum Charging Current | 8A for 30KW power module (User-djustable); 6A for 20KW power module (User-adjustable) | ||
Maximum Voltage | +/- 240V (12V x 40 Pcs) | ||
Nominal Voltage | +/- 216V (12V x 36 Pcs) | ||
Temperature Compensation | Yes | ||
Minimum Voltage | +/- 192V (12V x 32 Pcs) | ||
ENVIRONMENT | |||
Altitude | <1000m for Nominal power | ||
IP Class | IP 20 | ||
Operating Temperature | 0~40℃ | ||
Operating Humidity | 0~95% non-condensing | ||
PHYSICAL | |||
Cabinet Dimension (D x W x H) mm | 1000 x 515 x 763 | ||
Net Weight (kgs) | 182 | 183.5 | |
MANAGEMENT | |||
Optional SNMP | Power management from SNMP manager and web browser | ||
Smart RS-232 / USB | Supports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC | ||
STANDARDS | |||
Safety | IEC/EN 60950-1; IEC/EN 62040-1 |